Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 145

background image

Chapter 4 Parameters|

4-96

Revision August 2008, 03VE, SW V2.04

06-02

Phase-loss Protection

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Warn and keep operation

1

Warn and ramp to stop

2

Warn and coast to stop

It is used to set the phase-loss treatment. The phase-loss will effect driver’s control

characteristic and life.

06-03

Over-Current Stall Prevention during Acceleration

Unit: 1

Control

mode

VF

VFPG

SVC

Factory Setting: 170

Settings 00~250%

During acceleration, the AC drive output current may increase abruptly and exceed the value

specified by Pr.06-03 due to rapid acceleration or excessive load on the motor. When this

function is enabled, the AC drive will stop accelerating and keep the output frequency constant

until the current drops below the maximum value.

06-03

Over-Current
Detection

Level

Output
Frequency

Over-Current Stall
prevention during

Acceleration,
frequency held

time

actual acceleration time when over-current stall

prevention is enabled

current

06-04

Over-current Stall Prevention during Operation

Unit: 1

Control

mode

VF

VFPG

SVC

Factory Setting: 170

Settings

00 to 250%

If the output current exceeds the setting specified in Pr.06-04 when the drive is operating, the

drive will decrease its output frequency to prevent the motor stall. If the output current is lower

than the setting specified in Pr.06-04, the drive will accelerate again to catch up with the set

frequency command value.