Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04
4-151
10-02
PG Feedback Fault Treatment
Control
mode
VFPG
FOCPG
TQRPG
Factory Setting: 2
Settings
0
Warn and keep operating
1
Warn and RAMP to stop
2
Warn and COAST to stop
10-03
Detection Time for PG Feedback Fault
Unit: 0.01
Control
mode
VFPG
FOCPG
TQRPG
Factory Setting: 1.00
Settings
0.00 to 10.00 sec
When PG loss, encoder signal error, pulse signal setting error or signal error, if time exceeds
the detection time for PG feedback fault (Pr.10-03), the PG signal error will occur. Refer to the
Pr.10-02 for PG feedback fault treatment.
10-04
ASR (Auto Speed Regulation) control (P) 1
Unit: 0.1
Control
mode
VFPG
FOCPG
Factory Setting: 10
Settings
0 to 40 Hz
10-05
ASR (Auto Speed Regulation) control (I) 1
Unit: 0.001
Control
mode
VFPG
FOCPG
Factory Setting: 0.100
Settings
0.000 to 10.000 sec
10-06
ASR (Auto Speed Regulation) control (P) 2
Unit: 0.1
Control
mode
VFPG
FOCPG
Factory Setting: 10
Settings
0 to 40Hz
10-07
ASR (Auto Speed Regulation) control (I) 2
Unit: 0.001
Control
mode
VFPG
FOCPG
Factory Setting: 0.100
Settings
0.000 to 10.000 sec
10-08
ASR 1/ASR2 Switch Frequency
Unit: 0.01
Control
mode
VFPG
FOCPG
Factory Setting: 7.00
Settings
5.00 o 600.00Hz
ASR P determines Proportional control and associated gain (P). ASR I determines integral
control and associated gain (I).