Chapter 4 Parameters|

4-162

Revision August 2008, 03VE, SW V2.04

Hz

N-m

Fbase

11-05/11-06

Flux Weakening Curve

11-06

Gain Value of Flux Weakening Curve for Motor 2

Unit: 1

Control

mode

FOCPG

Factory Setting: 90

Settings

0 to 200%

11-07

Detection Time for Phase-loss

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0.20

Settings

0.01 to 600.00 sec

When the phase-loss occurs and exceeds this detection time, the fault code “PHL” will be

displayed. The AC motor drive will record the operation time during phase-loss.

When phase-loss occurs and Pr.11-07 is set to 0, it won’t display PHL and won’t execute

Pr.06-02.

When user sets this parameter to 0 or not factory setting, we won’t promise that all

characteristics will be the same as the 3-phase input.

If it is set to 0 or a larger number, it will short the life of rectifier and capacitors in the AC motor

drive.

11-08

Reserved

11-09

Level of Phase-loss

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 60.0

Settings 0.0

to

320.0




11-10

Speed Feed Forward Gain

Unit: 1