Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 148

Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04
4-99
5%
Pr.06-07,
Pr.06-10
Pr.06-08, 06-11
current
06-12
Current Limit
Unit: 1
Control
mode
FOCPG
TQRPG
Factory Setting: 150
Settings
0 to 250%
It is used to set the current limit.
06-13
Electronic Thermal Relay Selection (Motor 1)
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 2
Settings
0
Operate with a Inverter Motor (forced external cooling)
1
Operate with a Standard Motor (self-cooled by fan)
2
Disabled
06-27
Electronic Thermal Relay Selection (Motor 2)
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 2
Settings
0
Operate with a Inverter Motor (forced external cooling)
1
Operate with a Standard Motor (self-cooled by fan)
2
Disabled
It is used to prevent self-cooled motor overheats under low speed. User can use electrical
thermal relay to limit driver’s output power.
06-14
Electronic Thermal Characteristic for Motor 1
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 60.0
Settings
30.0 to 600.0 sec
06-28
Electronic Thermal Characteristic for Motor 2
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 60.0
Settings
30.0 to 600.0 sec