Chapter 4 Parameters|

4-110

Revision August 2008, 03VE, SW V2.04

Time

B.B.

output current A

Input B.B. signal

Stop output voltage

Disable B.B. signal

Waiting time 08.07

Speed Search

Synchronization speed detection

Output frequency
(H)

07-09 Current Limit
for Speed Search Speed

FWD Run

B.B. Search with minimum output frequency upward timing chart

Output voltage

(V)

B.B. Search with minimum output frequency upward timing chart

Output frequency(H)

Output voltage(V)

Output current

06-03

Over-Current Stall

Prevention
during Accel.

FWD Run

Time

Input B.B. signal

Stop voltage output

Disable B.B. signal

Waiting time Pr.07-08
Speed search
Synchronization speed detection

B.B.

A

07-09

Current Limit for Speed Search

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 150

Settings

20 to 200%

Following a momentary power loss, the AC motor drive will start its speed search operation

only if the output current is greater than the value set by Pr.8-07. When the output current is

less than the value of Pr.8-07, the AC motor drive output frequency is at “speed

synchronization point”. The drive will start to accelerate or decelerate back to the operating

frequency at which it was running prior to the power loss.

When executing speed search, the V/f curve is operated by group 1 setting. The maximum

current for the optimum accel./decel. and start speed search is set by Pr.07-09.