Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-163

Control

mode

FOCPG

Factory Setting: 0

Settings

0 to 100%

11-12

Speed Response of Flux Weakening Area

Unit: 1

Control

mode

FOCPG

Factory Setting: 65

Settings

0 to 150% (0: disable)

It is used to control the response speed for the flux weakening area. The larger number you

set, the faster response you will get.

11-13

Notch Filter Depth

Unit: 1

Control

mode

FOCPG

Factory Setting: 0

Settings

0 to 20 db

11-14

Notch Filter Frequency

Unit: 0.01

Control

mode

FOCPG

Factory Setting: 0.00

Settings

0.00 to 200.00

This parameter is used to set resonance frequency of mechanical system. It can be used to

suppress the resonance of mechanical system.

The larger number you set Pr.11-13, the better suppression resonance function you will get.

The notch filter frequency is the resonance of mechanical frequency.

11-15

Gain Value of Slip Compensation

Unit: 0.01

Control

mode

SVC

Factory Setting: 1.00

Settings

0.00 to 1.00

It is only valid in SVC mode.

When the AC motor drive drives the asynchronous motor, slip will increase when the load is

added. This parameter can be used to change frequency, lower slip and make the motor be

synchronous when running under rated current. When the output current is higher than no-load

current, the AC motor drive will adjust frequency by this parameter. If the actual speed is

slower than expected, please increase the setting or decrease the setting.

11-16

Low-pass Filter Time of Keypad Display

Unit: 0.001

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0.100