Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-109

Settings

0.1 to 5.0 sec

If the duration of a power loss is less than this parameter setting, the AC motor drive will

resume operation. If it exceeds the Maximum Allowable Power Loss Time, the AC motor drive

output is then turned off (coast stop).

The selected operation after power loss in Pr.07-06 is only executed when the maximum

allowable power loss time is

≤5 seconds and the AC motor drive displays “Lu”.

But if the AC motor drive is powered off due to overload, even if the maximum allowable power

loss time is

≤5 seconds, the operation mode as set in Pr.07-06 is not executed. In that case it

starts up normally.

07-08

Baseblock Time for Speed Search (BB)

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0.5

Settings

0.1 to 5.0 sec

When momentary power loss is detected, the AC drive will block its output and then wait for a

specified period of time (determined by Pr.07-08, called Base-Block Time) before resuming

operation. This parameter should be set at a value to ensure that any residual regeneration

voltage from the motor on the output has disappeared before the drive is activated again.

B.B.

A

Output frequency(H)

Output voltage(V)

Output current

07-09
Current Limit for
Speed Search

FWD Run

Time

B.B. Search with last output frequency downward timing chart

Input B.B. signal

Stop output voltage

Disable B.B. signal

Waiting time Pr.07-08
Speed search
Synchronization speed detection

7

7

Frequency command before B.B.