Frame D

3

V/T2 W/T3

R/L1

DC

DC +

( )

( )

-

POWER

S/L2 T/L3

-

+2

+1

MOTOR

IM


Main circuit terminals

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,

, +1, +2, -

Models

Wire

Torque

Wire Type

VFD110V23A-2

VFD110V43A-2

VFD150V43A-2

VFD150V23A-2

VFD185V23A-2

VFD185V43A-2

VFD220V43A-2

VFD220V23A-2

8-2 AWG

(8.4-33.6mm

2

)

30kgf-cm

(26in-lbf)

Stranded

copper only,

75

o

C

Frame E

W/T3

S/L2

R/L1

T/L3

+2

+1

U/T1 V/T2

(173in-lbf)

Screw Torque:

200kgf-cm

POWER

IM

MOTOR

3

POWER

ALARM

CHARGE

Main circuit terminals

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,

, +1, +2, -

Models

Wire

Torque

Wire Type

VFD300V43A-2

VFD370V43A-2

VFD450V43A-2

57kgf-cm

(49in-lbf)

VFD300V23A-2

VFD370V23A-2

VFD550V43C-2

VFD750V43C-2

4-2 AWG

(21.2-33.6mm

2

)

200kgf-cm

(173in-lbf)

Stranded

copper

only, 75

o

C

NOTE

#

To connect 6 AWG (13.3 mm

2

) wires, use Recognized Ring Terminals

2.4 Control Terminals