Variables and Flags Assignment and Request Commands • Serial
309
Publication 1398-PM601A-EN-P — October 2000
HOST M
O
DE
Serial
COM1 word
COM2 word
These commands set the serial parameters for the Operator Terminal (Com1) and the Programming Ter-
minal (Com2). The parameters are encoded as a bit map in the following format:
System
Command
Description
Flag/
Variable
Read/
Write
Personality
Module
ADDR
Returns the host axis identifier specified by the dip
switch. The value will be in the range of 0..63. (Zero
indicates no individual axis identifier.)
byte
R
N
HOST
TRUE if the programming terminal is in host mode. In
host mode, the ULTRA Plus or IQ will give less ver-
bose responses to some commands and will not supply
error message strings.
F
R/W
N
NOECHO
TRUE if the ULTRA Plus or IQ is not to echo incom-
ing characters in a full duplex mode.
The default state on power up is FALSE.
F
R/W
N
NOLF
TRUE if the ULTRA Plus or IQ is not to add a line-
feed (^J) to responses. If TRUE, only a carriage return
(^M) will be transmitted.
F
R/W
N
Bit
Description
Values
0, 1
Unused
2
0 = RS-232C
1 = RS-422
3
Unused
7, 6, 5, 4
Baud Rate
0000 = 1200
0001 = 2400
0010 = 4800
0011 = 9600 (default)
0100 = 19200
9, 8
Parity
00 = None
01 = Odd
10 = Even
10
Data Bits
0 = 7 Data Bits
1 = 8 Data Bits
11..15
Unused
Command
Description
Flag/
Variable
Read/
Write
Personality
Module
ABSMODE
TRUE to enable Absolute mode
F
R/W