Language Reference • Reference
Publication 1398-PM601A-EN-P — October 2000
WORDS
HSWEN
Home Switch Enable
Home
Purpose
Set if Home Switch input is enabled.
Syntax
variable = HSWEN
variable
The variable may be a nonvolatile flag Bn, a volatile flag Fn, or
another system flag.
Remarks
This flag is provided so that you can configure the standard home program (system
program 25) to your specific needs. This flag informs the home program that a home
switch is present. HSWEN is set in the Parameter menu, Inputs dialog box.
See Also
INDEXEN, Appendix A, System Programs
Example
F7 = HSWEN
IF HSWEN = ON º
HSWSTAT
Home Switch Status
Home
Purpose
Present status of the Home Switch input. This flag reports the home input status as
active or inactive. It does NOT report if the input is ON or OFF. The Home Switch
Active States parameter in the Parameter menu, Inputs dialog box determines if HSW-
STAT is active when the home switch input is ON or OFF.
Syntax
variable = HSWSTAT
variable
The variable may be a nonvolatile flag Bn, a volatile flag Fn, or
another system flag.
Remarks
This flag is provided primarily for use with the standard home routine. If a home pro-
gram was written for a specific machine, the program could test for I5 ON or OFF
rather than test this flag.
See Also
Appendix A, System Programs
Example
IF HSWSTAT = ON ...
F3 = HSWSTAT