2 setting aupc parameters, 1 target eb/no, 2 max range – Comtech EF Data CDM-625 User Manual
Page 312

CDM-625 Advanced Satellite Modem
Revision 15
Automatic Uplink Power Control (AUPC)
MN-CDM625
8–2
8.2 Setting AUPC Parameters
The important consideration is that EDMAC framing should be enabled.
Do these steps:
1. Use the SELECT: Configuration Mode menu to first select EDMAC framing. You may
select EDMAC as IDLE, or define the unit as an EDMAC Master or Slave.
2. Verify that the remote modem also has EDMAC framing enabled.
3. Set the nominal output power of the modem: Use the SELECT: Configuration Tx
POWER menu to select MANUAL mode, and then edit the displayed Tx output power level.
4. Select AUPC as the operating mode. At this point, you are prompted to define four key
parameters: Target Eb/No, Max Range, Alarm, and Demod Unlock.
8.2.1 Target Eb/No
This is value of Eb/No that you need to keep constant at the remote modem:
• The minimum value to enter is 0.0 dB. If the Eb/No falls below this value, the AUPC control
will increase the Tx output power, but will never exceed the value determined by the
parameter MAX RANGE.
• The maximum value to enter is 14.9 dB. If the Eb/No exceeds this value, the AUPC control
will reduce the Tx output power, but will never drop below the nominal value set.
• The default value is 3.0 dB.
• The resolution is 0.1 dB.
8.2.2 Max Range
This defines how much the modem is permitted to increase the output level, under AUPC
control:
• The minimum value to enter is 0 dB.
• The maximum value to enter is 9 dB.
• The default value is 1 dB.
• The resolution is 1 dB.