Grounding practices (cont.), Interlocking – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 94

2-54
Drive Installation
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
Grounding Practices (cont.)
The main grounding conductor(s) should be run separately from
power and signal wiring so that faults:
• do not damage the grounding circuit,
or
• will not cause undue interference with or damage to protection or
metering systems, or cause undue disturbance on power lines.
Identification of Types of Electrical Supplies – Grounded and
Ungrounded Systems
When dealing with an ungrounded, three-phase electrical supply
system, the cable insulation must be capable of handling not only the
phase to phase voltage, but also the voltage to ground if one of the
other phases develops a ground fault. In practice, the cable
insulation of an ungrounded, three-phase system must be good for at
least a continuous voltage of root three (1.732) times (1.1) times the
rated voltage of the supply. (1.732 x 1.1 = 1.9 times the rated line-
to-line voltage)
Ground Bus
The drive ground bus runs along the top of the drive at the front.
The ground bus is accessible at the top of each of the drive
enclosures when the enclosure door is opened (and the low voltage
compartment hinged out in the case of the DC link/fan cabinet). It is
the responsibility of the installer to ensure that the drive is grounded
properly, typically at the point on the ground bus in the cabling
cabinet, close to the line cable terminations.
Interlocking
Access to the medium voltage areas of the drive is restricted by the
use of key interlocking for safety.
At installation the key interlocking is set up so that access to the
medium voltage compartments of the equipment can only be made
when the upstream power is locked in the off position.
Additionally, the key interlocking prohibits the upstream power
being applied until the medium voltage drive’s access doors have
been closed and locked shut.
It is the responsibility of the installer to ensure that the key
interlocking is installed properly to the upstream equipment.