Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 489
Troubleshooting
7-51
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION
RECOMMENDED ACTIONS
2U1A Device Wrn
264
PWM RECTIFIER SGCT WARNING
FOR REDUNDANT DEVICE CAPABILITY
ONLY
This warning will occur during the initial
contactor closure, the diagnostic sequence
after a start command, or the diagnostic
sequence after a stop command. The
rectifier monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. The SGCT has smart diagnostics, so
the feedback may indicate short before
firing, and if the pulse is received and the
device is really shorted, the diagnostic will
toggle the feedback to let you know the
problem is with the device, or the power
supply for that device.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting warnings before
any destructive action is taken from the next
action. The main example of this is closing
the input contactor on a shorted bridge.
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
– NOTE: There is only the Redundant
option available on the Rectifier, and
only on 6P drives (SCR orPWM). You
can not have N-1 operation on the
rectifier since we can not control the line
voltage.
2U1B Device Wrn
270
2U1C Device Wrn
282
2U4A Device Wrn
267
2U4B Device Wrn
273
2U4C Device Wrn
285
2V3A Device Wrn
266
2V3B Device Wrn
272
2V3C Device Wrn
284
2V6A Device Wrn
269
2V6B Device Wrn
275
2V6C Device Wrn
287
2W2A Device Wrn
265
2W2B Device Wrn
271
2W2C Device Wrn
283
2W5A Device Wrn
268
2W5B Device Wrn
274
2W5C Device Wrn
286
2U1A Online Wrn
252
PWM RECTIFIER SGCT WARNING
FOR REDUNDANT DEVICES CAPABILITY
ONLY
This warning will occur during operation of
the drive. The drive has detected that the
feedback from the device was not correct,
and does not wait to determine the exact
problem. The drive polls the entire bridge 3
times before and 3 times after each gating
command. All 6 of these readings for each
device must be consistent for the warning to
occur. There is also a parameter called
Rectifier Device Diagnostic Delay (P266),
which allows you to change the number of
consecutive firings to eliminate nuisance
warnings. It will still poll 3 times before and
after each firing, but will now require the
condition to exist for the number of
consecutive firings set in the Diagnostic
Delay parameter for a warning to occur.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting warnings before
any destructive action is taken from the next
action
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
– Reset the drive and let the offline
diagnostics further define the problem
– For nuisance faults, contact the factory
about extending the Diagnostic Delay
– NOTE: There is only the Redundant
option available on the Rectifier, and
only on 6P drives (SCR orPWM). You
can not have N-1 operation on the
rectifier since we can not control the line
voltage.
2U1B Online Wrn
258
2U1C Online Wrn
276
2U4A Online Wrn
255
2U4B Online Wrn
261
2U4C Online Wrn
279
2V3A Online Wrn
254
2V3B Online Wrn
260
2V3C Online Wrn
278
2V6A Online Wrn
257
2V6B Online Wrn
263
2V6C Online Wrn
281
2W2A Online Wrn
253
2W2B Online Wrn
259
2W2C Online Wrn
277
2W5A Online Wrn
256
2W5B Online Wrn
262
2W5C Online Wrn
280