Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 132

background image

3-38

Operator Interface

7000A-UM150F-EN-P – June 2013

7000 “A” Frame


Figure 3.48 – Modify Bit Encoded Value


To be allowed to make changes to the parameter, the operator
interface must be set to an Access Level other than 'Monitor'. (You
will be able to view the screen; however, pressing the data entry keys
will have no effect). If you are not in the correct level, press the [F8]
key in order to gain access to the parameter. Refer to the section
entitled Enter/Modify an Access Level for further information on
the operation to change the level.


Having gained access, press the left/right cursor keys to move to the
various bits within the parameter. As each bit is selected, the name
of the bit is displayed. Use the up/down arrow keys to toggle the
state of the bit.


The new value is not sent to the drive until you exit the screen with
the [F10] key. Prior to this you can modify the new value by
repeating the above procedure, or you can cancel the change by
pressing the [F7] key. The CANCEL operation returns the new
value to that of the actual value.

Analog Ports


The drive contains a number of external analog ports to which you
can assign any parameter. To setup an analog port, use the up/down
arrow keys on the SETUP screen to select the 'Analog' option and
press the [enter] key.


This will display a screen as shown in Figure 3.49 . The screen
shows the current tags and their tag code, which are associated with
each of the analog ports. To change the tag attached to a port, use
the [cursor up] and [cursor down] keys to highlight the desired port
and press the [enter] key. (If nothing happens then you have not
gained the required access to make changes. Exit to the SETUP
screen and refer to the section entitled Enter/Modify an Access
Level
to gain access).