beautypg.com

Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 364

background image

6-60

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

Top of Integral Line Reactor and Input Starter Section

Ventilation Cover

Fans

Terminal Blocks

Fan Mounting Bracket

Ventilation Cover

Fans

Terminal Blocks

Fan Mounting Bracket


Figure 6.49 – Starter/Line Reactor Cabinet Fan Removal


1. Remove the top ventilation cover from the exterior of the cabinet.


2. Remove mounting screws and invert fan mounting bracket to expose

fan mounting hardware.


3. Unplug or disconnect fan leads from terminal blocks and replace fan.

4. Reassemble in the reverse order of removal.