Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 443
Troubleshooting
7-5
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
Conductivity Hi
(C-Frame Only)
227
The measured coolant conductivity is
greater than 2 μS/cm
3
.
– Verify that no foreign debris has entered
the system (iron piping, non-deionized
water, etc.)
– Change the de-ionizing cartridge and run
the system, verifying that the conductivity
is decreasing
Coolant Level Lo
(C-Frame Only)
228
The measured coolant level within the
reservoir has dropped below the second
(lowest) level sensor and the drive has
faulted. This sensor is set for the minimum
level required to ensure there will be no air
drawn into the system through the reservoir.
– Verify that the drive cooling system does
not have any coolant leaks – repair if
found
– Add the proper amount of de-ionized
water to get the level above the warning
sensor (de-ionized water will evaporate,
not the glycol)
Coolant Temp Hi
(C-Frame Only)
226
The measured coolant temperature has
exceeded 54°C (129°F).
– Verify the heat exchanger fans are
operating
– Verify that the thermostatic valve is fully
opened
– Check that all valves are in the normal
operating position
– Verify that the drive is operating within
specified load and ambient conditions
Coolant Temp Lo
(C-Frame Only)
225
The measured coolant temperature has
dropped below 4°C (40°F). It will not clear
until the coolant temperature reaches 10°C
(50°F). This fault will only occur if the drive
is not running, to stop you from starting with
a low coolant temperature. If you are
already running when the coolant level
drops, you will only get a warning.
– Verify that the thermostatic bypass valve
(V10) was not left open
– Verify that the ambient temperature
within the drive control room is not below
specification
– Warm up the control room ambient to get
the drive to an operational level