beautypg.com

Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 437

background image

Component Definition and Maintenance 6-133

7000 “A” Frame

7000A-UM150F-EN-P –June 2013

Time Estimations

 Operational Maintenance

0.5 hours per filter

 Annual Maintenance

 Initial Information Gathering

0.5 hours

 Physical Checks

– Torque Checks

2.0 hours

– Inspection

2.0 hours

– Cleaning **

2.5 hours **

– Meggering

1.5 hours

 Control Power Checks

Contactor Adjustments **

2.0 hours **

Voltage Level Checks

1.0 hours

Firing Check

0.5 hours

System Test **

2.0 hours **

 Medium Voltage Checks

Final Inspection

0.5 hours

Phasing Check **

1.5 hours **

Autotuning**

2.0 hours **

Operation to Maximum Load

Site Dependent

 Additional Tasks

Investigation **

Depends on Nature of the Problem **

Informal Training/Refresher **

2.0 hours **

Spare Parts Analysis **

1.0 hours **

Vacuum Bottle Integrity Check **

3.0 hours **

Final Report

3.0 hours

Note: ** indicates that the time may not be required depending on the
nature of the maintenance and the condition of the drive system. These