Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 436

6-132
Component Definition and Maintenance
7000A-UM150F-EN-P –June 2013
7000 “A” Frame
Additional Tasks During Preventive Maintenance
Investigation of customer‟s concerns relating to drive performance
Relate any problems found during above procedures to customer
issues.
Informal instruction on drive operation and maintenance for plant
maintenance personnel
Reminder of safety practices and interlocks on MV equipment,
and on specific operating concerns
Reminder of the need to properly identify operating conditions
Recommendation for critical spare parts which should be stocked in-
plant to reduce production downtime
Gather information on all spare parts on site, and compare that
with factory-recommended critical spares to evaluate whether
levels are sufficient.
Contact MV Spare Parts group for more information.
Vacuum Bottle Integrity Testing using a Vacuum Checker or AC
Hipot
Refer to Publication 1502-UM050_-EN-P for a detailed
description of all contactor maintenance.
Final Reporting
A complete, detailed report on all steps in the Preventive Maintenance
procedures should be recorded to identify changes.
A completed copy of this checklist should be included.
A detailed description of ALL ADJUSTMENTS AND
MEASUREMENTS that were taken during the process should be
included in an addendum (Interlock Adjustments, Loose
Connections, Voltage Readings, Megger Results, Parameters, etc.)
THIS INFORMATION SHOULD BE COMMUNICATED TO MV
PRODUCT SUPPORT SO THAT FUTURE SUPPORT
ACTIVITIES WILL HAVE THE LATEST SITE INFORMATION
AVAILABLE.
This can be faxed to (519) 740-4756
Annual Maintenance
(cont.)