Control power components, Ride-through – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 373

Component Definition and Maintenance 6-69
7000 “A” Frame
7000A-UM150F-EN-P –June 2013
Control Power Components
There are two configurations in which control power will be distributed
for the drive. The different methods are dependent on what drive option
the customer has chosen:
1. Integrated Line Reactor Drive with Integral Starter (refer to Figure 6.54)
2. Remote Transformer and Starter (refer to Figure 6.55)
3. Integrated Line Reactor Drive with Remote Starter (refer to Figure 6.55)
4. Integrated Transformer Drive (refer to Figure 6.56)
Ride-Through
Standard controls with 5 cycle ride-through – The drive main control
boards will remain energized for a total of 5 cycles after control power is
interrupted. If control power is not restored during the 5 cycles, a
controlled shutdown will occur.
Figure 6.54 illustrates the control power distribution for 6-pulse and PWM
drives with integral starter/line reactor.
* Up to 6 supplies depending on voltage and rectifier type
+24V I/O
DC/DC
Converter
20V Isolated
Gate Driver
Power Supply*
DC
FAIL
AC
FAIL
DC/DC
WARN
SPGDB P/S
FAIL
+5V - LOGIC
+/-15V - LOGIC
+/-24V – HALL EFFECT
+12V - REM I/O
+15V - TACH
20V
AC/DC
Converter
56 V DC
1500 W
DC/DC
FAIL
Fan
120V
1-ph
Printer
Creator Interface
Relays
VFD
380V 50Hz
or
460V 60Hz
3-ph
+15V SPGDB Test Power
and pressure transducer
* Up to 6 supplies depending on voltage and rectifier type
+24V I/O
DC/DC
Converter
20V Isolated
Gate Driver
Power Supply*
DC
FAIL
AC
FAIL
DC/DC
WARN
SPGDB P/S
FAIL
+5V - LOGIC
+/-15V - LOGIC
+/-24V – HALL EFFECT
+12V - REM I/O
+15V - TACH
20V
AC/DC
Converter
56 V DC
1500 W
DC/DC
FAIL
Fan
120V
1-ph
Printer
Creator Interface
Relays
VFD
380V 50Hz
or
460V 60Hz
3-ph
+15V SPGDB Test Power
and pressure transducer
Figure 6.54 – 6-pulse/PWM Line Reactor Drives with Integral Starter