beautypg.com

External input/output boards – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 398

background image

6-94

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

External Input/Output Boards

The External Input/Output (XIO) Boards are connected through a network
cable (CAN Link) to the Customer Interface Board. This cable may be
connected to either XIO Link A (J4) or XIO Link B (J5). The XIO board
handles all external Digital Input and Output signals and sends them to the
CIB through the cable. There are 16 Isolated Inputs and 16 Isolated
Outputs on the card, and they are used for Runtime I/O including Start,
Stop, Run, Fault, Warning, Jog, and External Reset signals. The boards
also handle the standard drive fault signals (Transformer/Line Reactor
Overtemperature, DC Link Overtemperature, etc.) and several spare
configurable fault inputs. There is an option in software to assign each
XIO a specific function (General IO, External IO or Liquid Cooling).


16 15 14 13 12 11 10 9

8 7 6 5 4 3 2 1

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

OUTPUTS

INPUTS

LEDS

Figure 6.72 – XIO Board