beautypg.com

Ac/dc power supply (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 378

background image

6-74

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

Terminal / Connections Descriptions

The terminal connections are shown in Figure 6.

59

.

Control signals

DC outputs

Single phase input

TOP

VIEW

FRONT

VIEW

Earth

Line

Neutral

Figure 6.59 – Terminal locations on AC/DC power supply

P1-AC input

PIN#

LABEL

1

EARTH

2

LINE

3

NEUTRAL

P2-DC output

PIN#

LABEL

1

+56V

2

+56V COMM

3

+56V

4

+56V COMM

P3-FAIL output

PIN#

LABEL

3

DC POWER FAIL (OUTPUT POWER GOOD)

14

AC/DC FAIL COMM (LOGIC RETURN)

15

CURRENT SHARING

16

AC POWER FAIL (POWER FAIL)

Ensure the output of the supply is 56V DC.

There is a potentiometer on the top of the power supply that adjusts the 56
Volt DC output for the power supply. Isolate the output of the power
supplies; multiple supplies in series will affect your measurements. With the
control power on and the output of the AC/DC Converter isolated from the
drive control, adjust the potentiometer until the output equals 56 volts DC.
Perform this test on each power supply. When all adjustments are complete,
re-connect the power supply to the circuit and re-measure the output. Adjust
if necessary.

If it is not possible to maintain 56 V DC, the power supply may be faulty.

AC/DC Power Supply

(cont.)