Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 468
![background image](/manuals/580302/468/background.png)
7-30
Troubleshooting
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
2U1A Online OC
342
6P or 18P SCR RECTIFIER FAULT
(Online Open-Circuit)
For SCR rectifiers, this fault will occur during
operation. After a firing signal is sent to a
device, the drive monitors the feedback
status to ensure the voltage drops to zero
across that device, indicating it has been
turned on. If the feedback does not drop to
zero before approximately 30-50 µsec, the
drive will assume the device is open and a
fault will occur. There is a 6 cycle fixed
delay, which means that this has to occur for
6 consecutive firings before the fault is
instigated.
– Complete a resistance check on the
rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors
– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the
sharing resistors
– Verify fiber optic integrity from FOI board
transmitter to SCRGD board receiver
– Replace all faulty components
2U1B Online OC
348
2U1C Online OC
390
2U4A Online OC
345
2U4B Online OC
351
2U4C Online OC
393
2V3A Online OC
344
2V3B Online OC
350
2V3C Online OC
392
2V6A Online OC
347
2V6B Online OC
353
2V6C Online OC
395
2W2A Online OC
343
2W2B Online OC
349
2W2C Online OC
391
2W5A Online OC
346
2W5B Online OC
352
2W5C Online OC
394
3U1B Online OC
414
3U4B Online OC
417
3V3B Online OC
416
3V6B Online OC
419
3W2B Online OC
415
3W5B Online OC
418
4U1C Online OC
420
4U4C Online OC
423
4V3C Online OC
422
4V6C Online OC
425
4W2C Online OC
421
4W5C Online OC
424