Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 488
7-50
Troubleshooting
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION
RECOMMENDED ACTIONS
U1A Device Wrn
228
INVERTER SGCT WARNING
FOR REDUNDANT DEVICES or N-1
CAPABILITY ONLY
This warning will only occur during the initial
contactor closure and the diagnostic
sequence after a start command. The
inverter monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. The SGCT has smart diagnostics, so
the feedback may indicate short before
firing, and if the pulse is received and the
device is really shorted, the diagnostic will
toggle the feedback to let you know the
problem is with the device, or the power
supply for that device.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting problems before
any destructive action is taken from the next
action
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed in matched
sets during the next outage
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
– NOTE: For Redundant devices, there
will be no change in the drive operation.
For N-1 drives, the drive will attempt to
run at a load/speed combination that
does not exceed the voltage rating of the
remaining devices.
U1B Device Wrn
234
U1C Device Wrn
246
U4A Device Wrn
231
U4B Device Wrn
237
U4C Device Wrn
249
V3A Device Wrn
230
V3B Device Wrn
236
V3C Device Wrn
242
V6A Device Wrn
233
V6B Device Wrn
239
V6C Device Wrn
251
W2A Device Wrn
229
W2B Device Wrn
235
W2C Device Wrn
247
W5A Device Wrn
232
W5B Device Wrn
238
W5C Device Wrn
250
U1A Online Wrn
216
INVERTER SGCT WARNING
FOR REDUNDANT DEVICES or N-1
CAPABILITY ONLY
This warning will occur during operation of
the drive. The drive has detected that the
feedback from the device was not correct,
and does not wait to determine the exact
problem. The drive polls the entire bridge 3
times before and 3 times after each gating
command. All 6 of these readings for each
device must be consistent for the warning to
occur. There is also a parameter called
Inverter Device Diagnostic Delay (P268),
which allows you to change the number of
consecutive firings to eliminate nuisance
faults. It will still poll 3 times before and
after each firing, but will now require the
condition to exist for the number of
consecutive firings set in the Diagnostic
Delay parameter for a warning to occur.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
– For nuisance faults, contact the factory
about extending the Diagnostic Delay
– NOTE: For Redundant devices, there
will be no change in the drive operation.
For N-1 drives, the drive will attempt to
run at a load/speed combination that
does not exceed the voltage rating of the
remaining devices.
U1B Online Wrn
222
U1C Online Wrn
240
U4A Online Wrn
219
U4B Online Wrn
225
U4C Online Wrn
243
V3A Online Wrn
218
V3B Online Wrn
224
V3C Online Wrn
242
V6A Online Wrn
221
V6B Online Wrn
227
V6C Online Wrn
245
W2A Online Wrn
217
W2B Online Wrn
223
W2C Online Wrn
241
W5A Online Wrn
220
W5B Online Wrn
226
W5C Online Wrn
244