Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 29
Overview of Drive 1-11
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
Description
Specifications
Control Power
220/240 V or 110/120 V, 1 phase – 50/60 Hz (20 Amp)
External I/O
16 Digital Inputs, 16 Digital Outputs
External Input Ratings
50/60 Hz AC or DC
120-240 V – 1 mA
External Output Ratings
50-60 Hz AC or DC
30-260 V – 1 amp
Analog Inputs
(1) Isolated, (1) Non-isolated, 4-20 mA or 0-10 V
Analog Resolution
• Analog input 12 Bit (4-20 mA)
• Internal parameter 32 Bit resolution
• Serial Communication 16 But resolution ( .1 Hz)
(Digital Speed Reference)
Analog Outputs
(1) Isolated, (7) Non-isolated, 4-20 mA or 0-10 V
Communication Interface
SCANPort /DPI
Scan Time
Internal ScanPort – 10 ms
Internal DPI – 5 ms
Communications Protocols
(Optional)
R I/O
Lon Works
DeviceNet
Can Open
Ethernet
RS485 HVAC
Profibus
RS485 DF1
Modbus
RS232 DF1
Modbus +
RS232 C
Interbus
Enclosure
NEMA 1, IP21
Lifting Device
Standard / Removable
Mounting Arrangement
Mounting Sill Channels
Structure Finish
Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking
Key provision for customer input Disconnecting Device
Corrosion Protection
Unpainted Parts (Zinc Plates / Bronze Chromate)
Fiber Optic Interface
Rectifier – Inverter – Cabinet (Warning/Trip)
Door Filter
Painted Diffuser with Matted Filter Media
Door Filter Blockage
Air Flow Restriction Trip/Warning
Ambient Temperature
0° to 40°C (32°F to 104°F)
Storage and Transportation
Temperature Range
-40°C to 70°C (-40°F to 185°F)
Relative Humidity
95% Non-Condensing
Altitude (Standard)
0 to 3300 ft. (0 to 1000 m)
Altitude (Optional)
0 to 16400 ft. (1001 to 5000 m)
Seismic (UBC Rating)
1, 2, 3, 4
Standards
NEMA, IEC, CSA, UL, ANSI, IEEE