beautypg.com

Uniform clamping pressure, Checking clamping pressure – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 323

background image

Component Definition and Maintenance 6-19

7000 “A” Frame

7000A-UM150F-EN-P –June 2013

Pressure on the SGCTs must be uniform to prevent damage and to ensure
low thermal resistance. Uniform pressure can be achieved by loosening
the heatsink mounting bolts, tightening the clamp and then tightening the
heatsink bolts. See section “Uniform Clamping Pressure” for instructions.


External filtered air will be directed through the slots of the heatsinks to
carry away the generated heat from the SGCTs. The door filter is
necessary to ensure the slots on the heatsinks do not get plugged.



Uniform Clamping Pressure

It is very important to maintain proper pressure on the thyristors. Follow
this procedure whenever changing devices, or whenever the clamp is
loosened completely.

1. Apply a thin layer of Electrical Joint Compound (Alcoa EJC No. 2 or

approved equivalent) to the clamp head pressure pad face.

2. Torque the heatsink bolts to 13.5 N-m (10 ft-lb.) and then loosen each

bolt two complete turns.

3. Tighten the clamp to the proper force until the indicating washers can

just be turned by the fingers with some resistance.

4. Torque the heatsink bolts to 13.5 N-m (10 ft-lb.) starting with the

center heatsink and moving outward alternating left to right.

5. Check clamp indicating washer.

Checking Clamping Pressure

Periodically, the clamping force in the PowerCage should be inspected.
Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main
power has been disconnected before working on
the drive. Verify that all circuits are voltage free
using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in
injury or death.