beautypg.com

Dimensions / weights, Nominal power ratings – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 39

background image

Overview of Drive 1-21

7000 “A” Frame

7000A-UM150F-EN-P – June 2013


Dimensions / Weights

Nominal Line

Voltage

Drive Type

VFD

Maximum

Current

Total Width

Approx. Weight

lb (kg)

Millimeters

Inches

2400V 60 Hz or
3300V 50 Hz or

4160V 50/60 Hz

Configuration #1 – Base Drive

160

2100

82.67

4300 (1955)

Configuration #2 – Base Drive with Integral Isolation

Transformer

160

2400

94.49

8300 (3765)

Configuration #3 – Base Drive with Integral Line Reactor

and Input Starter

160

2400

94.49

9800 (4455)

6600V 60 Hz

Configuration #1 – Base Drive

105

2400

94.49

6500 (2955)

Configuration #2 – Base Drive with Integral Isolation

Transformer

105

2800

110.24

10000 (4545)

Configuration #3 – Base Drive with Integral Line Reactor

and Input Starter

105

2800

110.24

7500 (3410)

Note:

Total Depth = 1000 mm (39.37 in.)

Total Height without fan shroud = 2275 mm (89.56 in.)

Total Height with fan shroud = 2583 mm (101.69 in.)

Nominal Power Ratings

Nominal Line Voltage

VFD Current Range

(Amps)

Nominal HP Range

Nominal kW Range

2400V 60 Hz

46 – 160

200 – 700

150 – 522

3300V 50 Hz

46 – 160

250 – 1000

187 – 750

4160V 50/60 Hz

46 – 160

350 – 1250

260 – 933

6600V 50 Hz

40 – 105

500 - 1250

400 – 933