7-28
Troubleshooting
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
2U1A Offline OC
366
6P or 18P SCR RECTIFIER FAULT
(Offline Open-Circuit)
For SCR rectifiers, this fault will occur after
the initial contact closure, or during the
diagnostic sequence after a start command.
After the Short-Circuit test described below,
the drive fires each device, and verifies that
the feedback from that device went low. If
the feedback does not go low, the drive
assumes the SCR must be Open-Circuited.
– Complete a resistance check on the
rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors
– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the
sharing resistors
– Verify fiber optic integrity from FOI board
transmitter to SCRGD board receiver
– Replace all faulty components
2U1B Offline OC
372
2U1C Offline OC
402
2U4A Offline OC
369
2U4B Offline OC
375
2U4C Offline OC
405
2V3A Offline OC
368
2V3B Offline OC
374
2V3C Offline OC
404
2V6A Offline OC
371
2V6B Offline OC
377
2V6C Offline OC
407
2W2A Offline OC
367
2W2B Offline OC
373
2W2C Offline OC
403
2W5A Offline OC
370
2W5B Offline OC
376
2W5C Offline OC
406
3U1B Offline OC
438
3U4B Offline OC
441
3V3B Offline OC
440
3V6B Offline OC
443
3W2B Offline OC
439
3W5B Offline OC
442
4U1C Offline OC
444
4U4C Offline OC
447
4V3C Offline OC
446
4V6C Offline OC
449
4W2C Offline OC
445
4W5C Offline OC
448