beautypg.com

Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 497

background image

Catalog Number Explanation – Drive Selection A-7

7000 “A” Frame

7000A-UM150F-EN-P – June 2013

Table A-7

Normal Duty and Heavy Duty Ratings / Dimensions Table

Nominal

Line

Voltage

Drive Type

and

Rectifier Type

VFD

Maximum

Current

(A)

Total Width

Approx.

Weight

lb (kg)

Structure

Code

(mm)

(inches)

2400V 60 Hz
3300V 50 Hz
4160V 50/60 Hz 

Base Drive, 6 Pulse or PWM rectifier

160

2100

82.67

4300 (1955)

71.7

Integral Transformer, 6 Pulse

or PWM rectifier

160

2400

94.49

4750 (2160)

71.3

Integral Line Reactor & Starter,
6 Pulse or PWM rectifier

160

2400

94.49

9800 (4455)

71.4

Integral Line Reactor,
6 Pulse or PWM rectifier

160

2400

94.49

4600 (2100)

71.11

6600V 50 Hz

Base Drive, 6 Pulse or PWM rectifier

105

2400

94.49

6500 (2955)

71.8

Integral Transformer, 6 Pulse
or PWM rectifier

105

2800

110

10000 (4545)

71.6

Integral Line Reactor & Starter,
6 Pulse or PWM rectifier

105

2800

110

7500 (3410)

71.5

Integral Line Reactor,
6 Pulse or PWM rectifier

105

2800

110

6350 (2880)

71.12

106 Amp rating is not available for drives rated at 4160V, 50 Hz.