6-130

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

Check for any visual/physical evidence of damage and/or degradation

of components in the low voltage compartments.

 This includes Relays, Contactors, Timers, Terminal connectors,

Circuit breakers, Ribbon cables, Control Wires, etc.; Causes could be
corrosion, excessive temperature, or contamination.

 Clean all contaminated components using a vacuum cleaner (DO

NOT use a blower), and wipe clean components where appropriate.

Check for any visual/physical evidence of damage and/or degradation

of components in the medium voltage compartments (inverter/rectifier,
cabling, DC Link, contactor, load break, harmonic filter, etc).

 This includes main cooling fan, power devices, heatsinks, circuit

boards, insulators, cables, capacitors, resistors, current transformers,
potential transformers, fuses, wiring, etc.; Causes could be corrosion,
excessive temperature, or contamination.

 Verify torque on heatsink bolts (electrical connections to bullet

assemblies) is within specifications (13.5 N-m).

 Clean all contaminated components using a vacuum cleaner (DO

NOT use a blower), and wipe clean components where appropriate.

 NOTE: An important component to check for contamination is the

heatsink. The fine grooves in the aluminum heatsinks can capture
dust and debris.

Carry out the physical inspection and verification for the proper

operation of the contactor/isolator interlocks, and door interlocks.

 Carry out the physical inspection and verification for the proper

operation of the key interlocks.

 Physical verification of the additional cooling fans mounted in the AC

Line Reactor cabinet, Harmonic Filter cabinet for mounting and
connections.

 Carry out the cleaning of the fans and ensure that the ventilation

passages are not blocked and the impellers are freely rotating without
any obstruction.

 Carry out the insulation meggering of the drive, motor, isolation

transformer/line reactor, and the associated cabling.

 Refer to User‟s Manual, Appendix D for meggering procedure.

Annual Maintenance

(cont.)