7-26
Troubleshooting
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
2U1A Fbk FO Loss
267
PWM RECTIFIER SGCT FAULT
(Feedback Fiber-Optic Loss)
This fault will occur during the initial
contactor closure, the diagnostic sequence
after a start command, or the diagnostic
sequence after a stop command. The
rectifier monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. This fault occurs when the feedback
was low from the device before gating, and
is still low from the device after gating. The
drive then assumes the feedback must be
the problem.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action
– Verify that the Feedback Fiber-Optic
from the SCGT to the FOI board is not
damaged or disconnected
– Verify that the Gate Pulse has been
received by the SGCT board using
Gating Test Mode
– Complete a resistance check described
in Chapter 4, checking the devices,
sharing resistors, and snubber circuitry
– Replace all faulty components
2U1B Fbk FO Loss
273
2U1C Fbk FO Loss
324
2U4A Fbk FO Loss
270
2U4B Fbk FO Loss
276
2U4C Fbk FO Loss
327
2V3A Fbk FO Loss
269
2V3B Fbk FO Loss
275
2V3C Fbk FO Loss
326
2V6A Fbk FO Loss
272
2V6B Fbk FO Loss
278
2V6C Fbk FO Loss
329
2W2A Fbk FO Loss
268
2W2B Fbk FO Loss
274
2W2C Fbk FO Loss
325
2W5A Fbk FO Loss
271
2W5B Fbk FO Loss
277
2W5C Fbk FO Loss
328
2U1A Gat FO Loss
279
PWM RECTIFIER SGCT FAULT
(Gating Fiber-Optic Loss)
This fault will occur during the initial
contactor closure, the diagnostic sequence
after a start command, or the diagnostic
sequence after a stop command. The
rectifier monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. This fault occurs when the feedback
was high from the device before gating, and
is still high from the device after gating. The
drive then assumes the gating pulse must
not have reached the device.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action
– Check that the fiber optic cables are
seated properly in the Optical Interface
Board and the SCGT firing card
– Check that the fiber optic cable is not
pinched or damaged
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify all the power connections to the
SCGT firing card are seated properly
2U1B Gat FO Loss
285
2U1C Gat FO Loss
330
2U4A Gat FO Loss
282
2U4B Gat FO Loss
288
2U4C Gat FO Loss
333
2V3A Gat FO Loss
281
2V3B Gat FO Loss
287
2V3C Gat FO Loss
332
2V6A Gat FO Loss
284
2V6B Gat FO Loss
290
2V6C Gat FO Loss
335
2W2A Gat FO Loss
280
2W2B Gat FO Loss
286
2W2C Gat FO Loss
331
2W5A Gat FO Loss
283
2W5B Gat FO Loss
289
2W5C Gat FO Loss
334