Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 420

background image

6-116

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

14. Press F5 [POST] key and enter 10 (this is the percentage of post-

trigger samples) and then press the Enter key.

15. Now, press F10 [EXIT] key to exit to „Diagnostic‟ screen. On the

„Diagnostics‟ screen, verify that the Status is „Running”, which means
the Diagnostic Trend is ready and will capture the data whenever the
trigger condition is satisfied. If the Status shows „Stopped‟ then press
F7 [Re-Arm] key. This will change the Status to Running.

16. Now press F10 [EXIT] to exit to the main screen.