Component Definition and Maintenance 6-115

7000 “A” Frame

7000A-UM150F-EN-P –June 2013

11. Press F2 [CONDITION] key. The cursor will move to the “=” equal

sign. This defines the trigger condition. Press up or down arrow keys
to select + sign as the trigger condition for our example.

12. Press F3 [DATA] key. The cursor moves to the data field. In our

example we will enter 18 and then press Enter key.

13. Press F4 [RATE] key. The cursor moves to the rate field. Here we

will enter 0, which is the fastest sample rate (1 msec/sample) and then
press Enter key.