6-108

Component Definition and Maintenance

7000A-UM150F-EN-P –June 2013

7000 “A” Frame

DOSFWDL

This is a DOS program which copies the .FMW file out the serial port of
the laptop to the serial port of the terminal. The program is usually
included in the firmware package. The method is described below. In this
example, we are using firmware file FRN_4006.FMW.

Note
: If you are using a newer firmware, just make sure the filename is
max 8 character long. You can rename the file, but keep the filename
extension as .FMW. Also, when you are prompted to enter the filename,
make sure you enter the correct filename as illustrated in the following
example.

Method

1. Make sure the Terminal is powered off. Disconnect Terminal‟s serial

cable connector from CIB board and connect it to the serial port on
your laptop. (You may need a gender changer.)


2. Turn on your laptop and run dosfwdl.exe program. On your laptop,

you should see the screen similar to one shown below.


3. Type in the firmware filename (e.g., FRN_4006.FMW) as shown in

the screen below and then hit Enter key.

4. Now, you will be prompted to enter Port address of your laptop.

Choose a correct port address and then hit Enter key.