Component Definition and Maintenance 6-91

7000 “A” Frame

7000A-UM150F-EN-P –June 2013


10. Apply control power to the drive. The CIBs are shipped with no

firmware installed, so the drive will automatically go into download
mode. Install firmware in the drive following the guidelines in
„Installing Firmware‟.


11. Program the drive. Refer to Technical Data “Medium Voltage AC

Drive Parameters” – publication 7000-TD001_-EN-P. The parameters
should also be saved to NVRAM and then externally to the drive
using the options described earlier in this section.

Signal Conditioning Boards

The Signal Conditioning Boards (SCB) receive all of the Analog Signals
from the drive‟s internal components. This includes the current and
voltage feedback signals. The boards also have isolated Digital I/O for
fan status, e-stops, and contactor control and status feedback. All of the
test points for the currents, system voltages, control voltages, and flux are
on these boards.

Figure 6.71 – SCB Board