Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 507
Logic Status Word
C-7
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
Product Specific Logic Command – Firmware 3.004 to 5.003
To be used with gateway adapters such as RIO or DeviceNet.
Bit
Function
Value
Description
Notes
0
Stop
1
Stop Drive using Stop Profile
1
Start (Pulsed)
1
Start Drive on rising edge using Start
Profile
2
Jog
1
Jog at default or Preset Speed
3
Clear Fault Queue
1
Clear Fault in Queue
4
Clear Warning Queue
1
Clear Warning in Queue
5
Reset Faults
1
Reset Faults and Warnings
7,6
Direction
0 1
Forward
1 0
Reverse
1 1
Not Used
8
DPI Local/Remote
Profile
0
Remote
All adapters can control the drive
(Full multiplexed control)
1
Local
Only the adapter that has been
granted permission has control of
the Drive (Includes XIO Front
Panel Selector Switch)
10,9
Synchronous Transfer
0 0
No Command
0 1
Transfer to Line
1 0
Transfer to Drive
1 1
Illegal
11
Start Profile
0
Accel 1 (Default)
Must be maintained until at
Speed.
1
Accel 2
12
Stop Profile
0
Decel 1 (Default)
Must be maintained until drive
stopped.
1
Decel 2
15-13
Speed Command Select
0 0 0
No Command
0 0 1
External Ref0 ( Front Panel Pot)
0 1 0
Preset 1
0 1 1
Preset 2
1 0 0
Preset 3
1 0 1
External Ref1 (Programmed Reference)
1 1 0
Manual Reference (Local DPI Adapter)
1 1 1
Not Used