Troubleshooting
7-39
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION
RECOMMENDED ACTIONS
HeatExchnger Fan
(C-FRAME ONLY)
144
The drive has detected a problem from the
Liquid-to-Air heat exchanger fans.
– Verify the Fan O/L settings and conditions
– Verify the Fan Control Relay status and
auxiliary contact signals.
Hub Comm Wrn
340
Hub (PLC) Communication Loss
– Check ControlNet adapter and cable
Inertia High
54
Indicates that the Autotune Inertia (P223)
was measured higher than 5.0 seconds.
– REFER TO THE POWERFLEX 7000
SERIES B MANUAL (CHAPTER 4 –
COMMISSIONING) ON AUTOTUNE
PROCEDURES, RESULTS, AND
ACTIONS
Input Close Dly
39
For PWM drives, this warning indicates that
a start command has been given, but the
drive is still waiting for the DC voltage to
discharge from the line filter capacitors.
This can be observed by the status
„Discharging‟, on the main screen. This time
can be based on the capacitor properties, or
Parameter 583 – Input Contactor Close
Delay (whichever is longer)
– Wait for the drive Ready status to
appear, allowing you to start the drive
– Verify the time in Parameter 583 is not
too long
Input Prot’n #1
65
Standard External Fault/Warning Input
included to allow the end-user to install a
protective relay (IE Input Feed Protection
Relay) auxiliary contact that can activate a
drive fault or warning, depending on
configuration of InputProt1 Class (P440).
– See associated Fault Description
Input Prot’n #2
70
Standard External Fault/Warning Input
included to allow the end-user to install a
second protective relay (IE Input Feed
Protection Relay) auxiliary contact that can
activate a drive fault or warning, depending
on configuration of InputProt2 Class (P445).
– See associated Fault Description
Input Xfmr/LR OT
66
The temperature switch in the drive Input
Isolation Transformer or Line Reactor has
detected an over-temperature and opened.
There is a thermal switch in each phase
winding, and they are connected in series.
– See associated Fault Description
Inv Heatsink FO
197
While Running, the Fiber Optic signal from
the TFB on the Inverter Heatsink, connected
to Channel A fiber optic receiver RX7 on
FOI-M-A is not present. This is only a fault
while not running. If this occurs while
running it will appear as a warning.
– Check TFB and FOI board for power
– Check the Fiber Optic cables are
properly seated in the transmitters and
receivers
– Check the fiber optic cable for kinks,
bends, breaks that could be blocking the
signal
– This can occur if the sensor is not
connected to the TFB
– NOTE: This is a warning because the
drive should not fault on the loss of the
signal while running. There is no
imminent danger to the drive, but the
user needs to be aware that there is a
temperature feedback signal missing.
Inv ChannelB FO
198
Not Normally Used: While Running, the
Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver
RX7 on FOI-M-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.