beautypg.com

Snubber capacitance (scr device) – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual

Page 213

background image

Commissioning 4-39

7000 “A” Frame

7000A-UM150F-EN-P – June 2013

Snubber Capacitance (SCR Device)


Using a capacitance meter, proceed to verify the snubber capacitor
by measuring from the test point and the white wire at the 2-pole
device snubber plug (labeled snubber).

Resistance between Test Point and white wire
at 2-pole plug is snubber capacitance





Figure 4.12 – Snubber Capacitance Test


To test the snubber capacitance, disconnect the plug of the self-
powered gate driver board labeled SHARING and SNUBBER. The
resistance between the white wire of the plug and the Test Point to its
left is the snubber capacitance.


Refer to Table 4.B to determine the appropriate snubber capacitance
value for the current rating of the SCR used. You should read the
actual snubber capacitor value shown in the table.


If the capacitor is found to be out of tolerance, refer to Chapter 6 –
Component Definition and Maintenance for detailed instructions on
how to replace the snubber capacitor.

Sharing Resistance

Snubber Resistance

Snubber Capacitor

Testpoint

To Gate
Driver Board

Heatsink

Heatsink

Sharing Resistance

Snubber Resistance

Snubber Capacitor

Testpoint

To Gate
Driver Board

Heatsink