beautypg.com

Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 70

background image

4Ć12

4.3.1

Deciding on a Data Communication Rate

Choosing a data communication rate for a remote I/O link not only

specifies the rate at which data is transmitted between the scanner

and adapters but also affects how far apart you can space the

control system components.
When choosing a data communication rate, make sure of the

following:
D all devices on the remote I/O link are capable of communicating

at that rate

D the communication rate meets your application requirements for

speed

D the maximum length of the remote I/O link, as determined by the

communication rate, is sufficient for connecting your I/O

The PC3000 can communicate at 57.6, 115.2, or 230.4 Kbps.

4.3.2

Determining the Required Cable Lengths and

Terminating Resistors

A remote I/O network must be configured as a daisychain

configuration.

Figure 4.7 Ć Daisychain Configuration

The length of the remote I/O link is interdependent with the data

communication rate. Refer to Table 4.2 for the required remote I/O

link cable lengths.

Table 4.2 Ć Remote I/O Link Distances Per Data Communication Rate

A remote I/O link using this data

communication rate (Kbps):

Cannot exceed this cable length:

57.6

3,048 m (10,000 ft)

115.2

1,524 m (5,000 ft)

230.4

762 m (2,500 ft)

This manual is related to the following products: