To configure the PC3000
as a passiveĆlistening drop,
remove the jumper.
Must be ON, unless you
are using the PC3000
as a passiveĆlistening
drop on the DCSĆNET
Network.
JP4
JP4
Figure 12.2 Ć Removing Jumper JP4
Step 3.
Power up the PC3000.
After the AutoMax PC3000 powers up, its DCSĆNET
network drop number is 56. The PC3000 now acts as a
passive listener on the DCSĆNET network.
To reĆconfigure the AutoMax PC3000 as a regular drop on the
DCSĆNET network, follow these steps:
Step 1.
Remove power to the Processor card.
Step 2.
Replace jumper JP4. See figure 12.2. If you need to
remove the card to access the jumper, follow the
procedures in sections 20.2.1 and 20.2.3.
Step 3.
Power up the PC3000.
After the PC3000 powers up, the DCSĆNET network drop
number is set to the factoryĆsetting of 55.
Step 4.
If necessary, change PC3000's network drop number by
following the procedures in section 12.3.
12.9
What to Do Next
You must configure the AĆB remote I/O scanner interface if you will
be controlling AĆB remote I/O. See chapter 13. Otherwise, begin
writing and implementing your application programs.