Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual
Page 188
18Ć6
Registers
Description
Registers 4 Ć 7
(Drop Status Bits)
(Continued)
0 0
15 14
0 0
13 12
0 0
11 10
0 0
9 8
0 0
7 6
0 1
5 4
1 1
3 2
0 1
1 0
Figure 18.2 Ć Register 4 in Drop 02 Slave Module
Indicating Drops 2, 3, and 4 Actively
Communicating With Master
At powerĆup, the Processor sets the drop depth of the
slaves to 1" to permit remote access to the Processor.
The drop 0 status bit in the slaves and the drop status bits
in the master will not be set.
After a user application task has defined drop depth, the
status bits in the slaves will be set to indicate the drops it
represents. The drop 0 status bit will also be set. In the
master, the drop status bits will be set to indicate all active
drops on the network.
Register 12 Ć
Drop Number
This register stores the drop number you set with the
Change Drop command. See section 12.3.2 for more
information about changing the drop. Bit 15 is set when a
valid drop number is assigned.
Register 14 Ć
Messages
Received
This register reflects the total number of messages
received by that module. While the line is inactive, this
value will remain unchanged. While the line is active, it will
constantly increase to 65535 and then roll over to zero.
Register 15 Ć
Receive Timeouts
When an active drop on the network is set up to receive, a
timer is set. If a message is not received before the timer
expires, a receive timeout occurs and is logged in this
register. The system allows for four consecutive timeouts
before it writes fault code C" to error code register 2001
in the Application Interface or on the Processor Info.
screen.
Register 16 Ć
CRC Errors
The SCC performs an errorĆchecking routine called a
Cyclic Redundancy Check (CRC) as a result of the SDLC
protocol. Any message received that is flagged with a
CRC error is ignored and no reply is transmitted. This
results in a reĆtransmission of the message. The value in
this register will increment if a CRC error occurs. This
value should ideally remain zero.
Register 17 Ć
Overrun Errors
The value in this register will increment if the buffer in the
SCC is filled and no read of the data has occurred. This
value should ideally remain zero.
Register 18 Ć
Abort Errors
The abort sequence feature of the SDLC protocol is not
used in the transmission routine. Therefore, if an abort is
detected in a receiver, there has been error. The value in
this register will increment with each abort error detected.
This value should ideally remain zero.