Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual
Page 262

DĆ10
Block Transfer Status, Request, and Control
(4 words per block transfer request)
Register:
Bit:
Function:
Access:
Block Transfer 1
835
Update time for Block
Transfer 1
To specify a nonĆcontinuous
block transfer, enter a value of
0.
To specify a continuous
block transfer, enter the time
interval.
Time interval (ms) = x*10,
where x is the value you enter
in this register.
read/write
Block Transfer 2
836Ć839
Block transfer 2ĊStatus and
Control Table
read/write
Block Transfer 3
840Ć843
Block transfer 3ĊStatus and
Control Table
read/write
Block Transfer 4
844Ć847
Block transfer 4ĊStatus and
Control Table
read/write
Block Transfer 5
848Ć851
Block transfer 5ĊStatus and
Control Table
read/write
Block Transfer 6
852Ć855
Block transfer 6ĊStatus and
Control Table
read/write
Block Transfer 7
856Ć859
Block transfer 7ĊStatus and
Control Table
read/write
Block Transfer 8
860Ć863
Block transfer 8ĊStatus and
Control Table
read/write
Block Transfer 9
864Ć867
Block transfer 9ĊStatus and
Control Table
read/write
Block Transfer 10 868Ć871
Block transfer 10ĊStatus and
Control Table
read/write
Block Transfer 11 872Ć875
Block transfer 11ĊStatus and
Control Table
read/write
Block Transfer 12 876Ć879
Block transfer 12ĊStatus and
Control Table
read/write
Block Transfer 13 880Ć883
Block transfer 13ĊStatus and
Control Table
read/write
Block Transfer 14 884Ć887
Block transfer 14ĊStatus and
Control Table
read/write
Block Transfer 15 888Ć891
Block transfer 15ĊStatus and
Control Table
read/write
Block Transfer 16 892Ć895
Block transfer 16ĊStatus and
Control Table
read/write
Block Transfer 17 896Ć899
Block transfer 17ĊStatus and
Control Table
read/write
Block Transfer 18 900Ć903
Block transfer 18ĊStatus and
Control Table
read/write