9 chaning the remote i/o data communication rate, 10 what to do next, 9 changing the remote i/o data communication rate – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual
Page 217

19Ć25
JP5
JP2
20843ĆM
To remove the operating
system, remove
the jumper.
Must be ON, unless you are
removing the operating
system from the PC3000.
JP5
Figure 19.3 Ć Removing Jumper JP5
19.9
Changing the Remote I/O Data
Communication Rate
Once you set the remote I/O data communication rate for the
scanner module, you should avoid changing the rate. If you must
use a rate different from the one you originally set, follow these
steps:
Step 1.
Stop all running programs in the AutoMax chassis.
Step 2.
Make sure that all adapters on the remote I/O link are
configured for the new data communication rate. All
devices on a remote I/O link must be communicating at
the same rate.
Step 3.
Define a new data communication rate for the scanner
module within the scanner initialization program. See
section 16.1.1.
Step 4.
Cycle power to the scanner module.
Step 5.
ReĆrun the scanner module's initialization program.
The new data communication rate takes effect after the scanner
module initialization program has finished.
19.10 What to Do Next
Schedule regular maintenance for the PC3000. Refer to chapter 20
as needed.