14.0 CONFIGURING AND

PROGRAMMING BLOCK

DATA TRANSFERS TO AĆB

I/O MODULES

For information about:

See this section:

About BlockĆTransfers

14.1

Configuring BlockĆTransfers

14.2

Programming BlockĆTransfers

14.3

Monitoring BlockĆTransfer Status

14.4

What to Do Next

14.5

14.1

About BlockĆTransfers

Many I/O modules and remote I/O adapters, such as analog

modules and operator interfaces, communicate to scanners solely

by blockĆtransfer. A blockĆtransfer operation allows the transfer of a

block of data to or from an I/O module during one remote I/O scan.

A maximum of 64 words can be transferred during one request, and

you can program a maximum of 48 blockĆtransfer requests. One

request can be processed per rack per remote I/O scan, but

multiple requests to a rack can be initiated.
When programming a blockĆtransfer, you specify whether it is a

continuous or nonĆcontinuous read or write request.

14.1.1

About BlockĆTransfer Read and Write Requests

The AutoMax PC3000 can perform biĆdirectional blockĆtransfers,

meaning it can issue blockĆtransfer read and blockĆtransfer write

requests. You must specify blockĆtransfer read operations when you

want to gather input and status data from the module and

blockĆtransfer write operations when you want to send output or

configuration data to the module.