Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 8
Table 94 - Bus Status Indicator
Table 95 - Temperature Fault Status Indicator
Table 96 - Shunt Fault Status Indicator
Table 97 - All Shunt Module Status Indicators
Bus Status Indicator
Status
Potential Cause
Possible Resolution
Flashing
Normal condition when control power is applied and bus voltage is less than 60V DC.
N/A
Steady Green
Normal condition when control power is applied and bus voltage is greater than 60V DC.
N/A
Off
Control power is not present.
Internal power supply failure.
Replace shunt module.
Over-Temp Fault
Indicator
Status
Potential Cause
Possible Resolution
Off
Normal condition.
N/A
Steady Red
Shunt module internal
temperature exceeds operating
temperature specification.
Shunt module fan failed.
Replace shunt module.
Shunt module temperature exceeds rating.
• Wait for shunt module to cool.
• Reset faults.
• Verify IAM module bus regulator configuration.
External over temperature
condition.
External temperature switch is open.
• Wait for shunt module to cool.
• Reset faults.
• Verify IAM module bus regulator configuration.
TS jumper is not present.
Install jumper.
Shunt Fault Indicator
Status
Potential Cause
Possible Resolution
Off
Normal condition
N/A
Steady Red
Shorted internal or external shunt
resistor.
Mis-wired shunt jumper or other short on RC
connector.
• Correct mis-wire (shorted) condition.
• If problem persists, replace shunt module.
Mis-wired (shorted) external shunt wiring.
Shunt Module Status
Indicator
Status
Potential Cause
Possible Resolution
• Bus Status
• Over-Temp Fault
• Shunt Fault
All three status indicators flash
simultaneously.
Shunt module hardware failure.
• Cycle power.
• If problem persists, replace shunt module.