Control module status indicators, Control module status indicators on, Control module status – Rockwell Automation 2094-EN02D-M01-Sx Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual User Manual
Page 209: Indicators
Rockwell Automation Publication 2094-UM002E-EN-P - May 2012
209
Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 8
Control Module Status Indicators
Table 87 - Drive Status Indicator (sercos control modules)
Table 88 - Comm Status Indicator (sercos control modules)
Table 89 - Bus Status Indicator
Condition
Drive Status
Possible Resolution
Off
No power
Apply power.
Alternating green/red
Self-test (power-up diagnostics)
Wait for steady green.
Flashing green
(1)
Standby (device not configured)
Wait for steady green.
Steady green
Normal operation, no faults
N/A
Flashing red
Minor fault (recoverable)
Refer to four-character fault message.
Steady red
Major fault (non-recoverable)
Refer to four-character fault message.
(1) This condition is the same as sercos ring phases 0, 1, 2, and 3.
Condition
Drive Status
Potential Cause
Possible Resolution
Off
No communication
(1)
Loose fiber-optic connection.
Verify proper fiber-optic cable connections.
Broken fiber-optic cable.
Replace fiber-optic cable.
Receive fiber-optic cable connected to sercos transmit
connector and vice versa.
Check proper sercos fiber-optic cable connections.
Flashing green
(2)
Establishing communication
System is still in the process of establishing sercos
communication.
Wait for steady green indicator.
Node address setting on the drive module does not
match sercos controller configuration.
Verify proper node switch setting.
Steady green
Communication ready
No faults or failures.
N/A
Steady red
No communication
Duplicate node address
Verify proper node addressing. Refer to
.
(1) Refer to Fiber-optic Cable Installation and Handling Instructions, publication
, for more information.
(2) This condition is the same as sercos ring phases 1, 2, and 3.
Condition
Bus Status
Condition
Off
No power or DC bus is not present.
• Normal when bus power is not applied.
• Fault exists, refer to
troubleshooting on
.
Bus power is present in follower IAM.
• Follower IAM power module is not configured as CommonBus Follow in RSLogix 5000 software.
• After DC bus voltage is applied, a 2.5 second delay before the indicator begins flashing green is
normal operation to provide the common-bus leader module time to complete pre-charge.
Flashing green
Bus power is present, axis disabled.
No major faults.
Normal when:
• 24V is not applied to Hardware Enable Input.
• MSO instruction is not commanded in RSLogix 5000 software.
Steady green
Bus power is present, axis enabled.
No major faults.
Normal when:
• 24V is applied to Hardware Enable Input.
• MSO instruction is commanded in RSLogix 5000 software.