Connecting the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 5
This example applies to a common-bus follower IAM power module.
Figure 56 - IAM Power Module (IPD connector)
Table 55 - Input Power (IPD) Connections
Table 56 - Termination Specifications
ATTENTION: Make sure the common-bus power connections are correct when
wiring the IPD connector plug and that the plug is fully engaged in the module
connector. Incorrect wiring/polarity or loose wiring can cause explosion or
damage to equipment.
DC-
DC+
L3
L2
L1
1 2 3 4 5 6
Bulletin 2094
IAM Power Module, Top View
IPD Connector
(IAM or follower IAM module)
IPD Pin
Signal
6
N.C.
5
N.C.
4
N.C.
3
2
DC+
1
DC-
IMPORTANT
Do not connect three-phase input power to the common-bus follower IAM
module.
IAM Module Cat. No.
Input VAC
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2094-BC01-Mxx-M
2094-BC02-M02-M
460V AC
2.5 (14)
10 (0.38)
1.2…1.5
(10.6…13.2)
2094-BC04-M03-M
6 (10)
16 (0.63)
2.4…3.0
(21.6…26.5)
2094-BC07-M05-M
30 (3)