Ethernet cable connections – Rockwell Automation 2094-EN02D-M01-Sx Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual User Manual
Page 135
Rockwell Automation Publication 2094-UM002E-EN-P - May 2012
135
Connecting the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 5
Ethernet Cable Connections
This procedure assumes you have your ControlLogix or CompactLogix
EtherNet/IP module and Bulletin 2094 control modules mounted and are ready
to connect the Ethernet network cables.
The EtherNet/IP network is connected by using the PORT 1 and/or PORT 2
connectors.
Table 78 - EtherNet/IP Connector Location
Shielded Ethernet cable is available in lengths up to 78 m (256 ft). However, the
total length of Ethernet cable connecting drive-to-drive, drive-to-controller, or
drive-to-switch must not exceed 100 m (328 ft).
If the entire channel is constructed of stranded cable (no fixed cable), then this is
the equation for calculating maximum length:
Maximum Length = (113-2N)/y, meters
where N = the number of connections in the channel
and y = the loss factor compared to fixed cable (typically 1.2…1.5).
Figure 81 - ControlLogix and CompactLogix Ethernet Port Locations
The 1756-EN
xT EtherNet/IP modules accept linear and star network
configurations. The 1756-EN
xTR modules and CompactLogix 5370 controllers
accept linear, ring (DLR), and star network configurations.
Drive Family
Cat. No.
EtherNet/IP Network
Refer to
Kinetix 6500
2094-EN02D-M01-Sx
Programming the safety configuration and the
RSLogix 5000 software program
Kinetix 6200
2094-SE02F-M00-Sx
Programming the safety configuration
Kinetix 6000M
2094-SEPM-B24-S
Monitoring, diagnostics, and firmware upgrades
1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
ControlLogix Platform
1756-ENxT EtherNet/IP module is shown.
ControlLogix Ethernet Ports
The 1756-EN2T modules have only one port,
1756-EN2TR and 1756-EN3TR modules have two.
Bottom Views
Front Views
CompactLogix 5370 L1, L2, and L3 Controllers
1769-L36ERM controller is shown.
Port 1, Front
Port 2, Rear
IMPORTANT
When using an external Ethernet switch for routing traffic between the
controller and the drive, switches with IEEE-1588 time synchronization
features must be used.