Configuring robot and power rail health checks – HP StoreEver ESL G3 Tape Libraries User Manual

Page 167

background image

1.

Locate the required tools:

#1 Phillips screwdriver

Air filter

2.

Take the library offline.

For information about taking the library offline, see

“Changing the library state” (page 93)

.

3.

On the operator panel, press Robotics Enabled to turn off power to the picker and return it to
the home position.

The power is on to all other components.

4.

Open the access door.

Aisle power is disabled.

5.

Use the Phillips screwdriver to unscrew the two captive thumbscrews. The screws remain
attached to the retaining bar.

6.

Remove the air filter.

7.

Use water and a mild soap to clean the air filter.

8.

Allow the air filter to dry.

NOTE:

Ensure that the air filter is completely dry before placing it back in the access door.

9.

Place the filter in the opening.

10.

Place the retaining bar over the filter to hold it in place. Use the Phillips screwdriver to tighten
the two captive thumbscrews.

11.

Close the access door.

12.

On the operator panel, press Robotics Enabled to enable the picker.

13.

Bring the library online. See

“Changing the library state” (page 93)

.

Configuring robot and power rail health checks

In Hardware Revision 2 libraries only, the library automatically performs health checks on the
robots and the robotic power rails. If problems are found, an event is generated.

By default, the library performs each check once per day. You can change how often the library
performs these checks. The interval can be set in increments of days, from once per day to once
per year. You can also set it to never run. HP recommends a once-per-day health check for the
robots and power rails. In dual robot libraries, it is important that the robots be properly installed
and tested to ensure that both robots are operating as designed.

1.

From the menu bar, select Setup

→Library Settings→Health Check Intervals.

The Health Check Intervals window displays the intervals for rails, active robot, and passive
robot (if applicable).

2.

Change any of the intervals by entering a new value in the field. The health check is performed
every time the interval has elapsed. If you enter zero, the health check will never be performed.

Configuring robot and power rail health checks