Branch circuit protection devices, D.2 ul standards, Table d.4 recommended input fuse selection – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 454

D.2 UL Standards
454
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75
°C 600 Vac UL-approved vinyl-sheathed insulation.
■
Branch Circuit Protection Devices
Table D.4 Recommended Input Fuse Selection
6 AWG
M4
14-NK4
YA-4
AD-902
TP-014
100-054-033
M5
R14-5
YA-4
AD-902
TP-014
100-054-034
M6
R14-6
YA-5
AD-952
TP-014
100-051-261
M8
R14-8
YA-5
AD-952
TP-014
100-054-035
4 AWG
M6
R22-6
YA-5
AD-953
TP-022
100-051-262
M8
R22-8
YA-5
AD-953
TP-022
100-051-263
3/2/1 AWG
M8
R38-8
YA-5
AD-954
TP-038
100-051-264
M10
R38-10
YA-5
AD-954
TP-038
100-061-114
1/0 AWG
1/0 AWG
× 2P
M8
R60-8
YA-5
AD-955
TP-060
100-051-265
M10
R60-10
YF-1, YET-300-1
TD-321, TD-311
TP-060
100-051-266
2/0 AWG
2/0 AWG
× 2P
M10
70-10
YF-1, YET-300-1
TD-323, TD-312
TP-080
100-054-036
1 AWG
× 2P
2 AWG
× 2P
M10
38-L10
YF-1, YET-150-1
TD-224, TD-212
TP-038
100-051-556
3/0 AWG
M10
80-10
YF-1, YET-300-1
TD-323, TD-312
TP-080
100-051-267
3/0 AWG
× 2P
M10
80-L10
YF-1, YET-150-1
TD-227, TD-214
TP-080
100-051-557
M12
80-L12
YF-1, YET-300-1
TD-323, TD-312
TP-080
100-051-558
4/0 AWG
M10
R100-10
YF-1, YET-300-1
YF-1, YET-150-1
TD-324, TD-312
TD-228, TD-214
TP-100
100-051-269
4/0 AWG
× 2P
M10
100-L10
YF-1, YET-150-1
TD-228, TD-214
TP-100
100-051-559
M12
100-L12
YF-1, YET-300-1
TD-324, TD-312
TP-100
100-051-560
250 / 300 kcmil
M10
R150-10
YF-1. YET-150-1
TD-229, TD-215
TP-150
100-051-272
M12
R150-12
YF-1, YET-300-1
TD-325, TD-313
TP-150
100-051-273
250 kcmil
× 2P
300 kcmil
× 2P
M10
150-L10
YF-1, YET-150-1
TD-229, TD-215
TP-150
100-051-561
M12
150-L12
YF-1, YET-300-1
TD-325, TD-313
TP-150
100-051-562
350 kcmil
M10
180-10
YF-1, YET-300-1
TD-326, TD-313
TP-200
100-066-687
400 kcmil
M10
200-10
YF-1, YET-300-1
TD-327, TD-314
TP-200
100-051-563
350 kcmil
× 2P
M12
180-L12
YF-1, YET-300-1
TD-326, TD-313
TP-200
100-066-688
400 kcmil
× 2P
M12
200-L12
YF-1, YET-300-1
TD-327, TD-314
TP-200
100-051-564
500 kcmil
600 / 650 kcmil
500 kcmil
× 2P
600 kcmil
× 2P
M10
325-10
YF-1, YET-300-1
TD-328, TD-315
TP-325
100-051-565
M12
325-12
YF-1, YET-300-1
TD-328, TD-315
TP-325
100-051-277
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user
should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG
× 2P for both input and output require two sets for input terminals and two sets for output terminals, so the
user should order four sets of [100-051-560].
Drive Model
CIMR-LE
L1000E
Nominal Output
Power HP
AC Drive Input
Amps
MCCB Rating
Amps
Time Delay Fuse
Rating Amps
Non-time Delay
Fuse Rating Amps
Bussmann
Semi-conductor Fuse Rating
(Fuse Ampere)
240 V Models
2A0018
5
15.6
25
25
40
FWH-90B (90)
2A0022
7.5
18.9
35
30
50
FWH-90B (90)
2A0031
10
28
50
40
75
FWH-100B (100)
2A0041
15
37
60
60
100
FWH-200B (200)
2A0059
20
52
100
90
150
FWH-200B (200)
2A0075
25
68
125
110
200
FWH-200B (200)
2A0094
30
80
150
125
225
FWH-300A (300)
2A0106
40
82
150
125
225
FWH-300A (300)
2A0144
50
111
200
175
250
FWH-350A (350)
2A0181
60
136
250
225
350
FWH-400A (400)
2A0225
75
164
300
250
450
FWH-400A (400)
2A0269
100
200
400
350
600
FWH-600A (600)
Wire Gauge
Terminal Screws
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
Machine No.
Die Jaw