S3-21: dwell 2 end speed, S3-25: dc injection gain in regenerative operation, S3-26: dc injection gain in motoring operation – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 253: 11 s: elevator parameters

5.11 S: Elevator Parameters
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
253
P
a
ra
me
te
r De
ta
ils
5
■
S3-21: Dwell 2 End Speed
The Dwell 2 function will end when the drive reaches this speed. A setting of 0.00 will disable the acceleration rate switch
that occurs at the end of Dwell 2.
■
S3-25: DC Injection Gain in Regenerative Operation
In OLV Control, S3-25 sets a gain level for DC Injection at stop (S1-03) for when the regenerative load reaches 100%. At
that time, the current applied during DC Injection at stop is determined as S1-03
× S3-25.
■
S3-26: DC Injection Gain in Motoring Operation
In OLV Control, S3-26 sets a gain level for DC Injection at stop (S1-03) when the motoring load reaches 100%. At that
time, the current applied during DC Injection at stop is determined as S1-03
× S3-26.
■
S3-27: Torque Compensation Value with Load Condition 1
Adjusts the analog signal from a load sensor for torque compensation.
Refer to Adjusting the Torque Compensation at
for details.
■
S3-28: Torque Compensation Value with Load Condition 2
Adjusts the analog signal from a load sensor for torque compensation.
Refer to Adjusting the Torque Compensation at
for details.
■
S3-29: Analog Input from Load Sensor with Load Condition 1
Adjusts the analog signal from a load sensor for torque compensation.
Refer to Adjusting the Torque Compensation at
for details.
■
S3-30: Analog Input from Load Sensor with Load Condition 2
Adjusts the analog signal from a load sensor for torque compensation.
Refer to Adjusting the Torque Compensation at
for details.
No.
Parameter Name
Setting Range
Default
S3-21
Dwell 2 End Speed
0.00 to 100.00%
0.00%
No.
Parameter Name
Setting Range
Default
S3-25
DC Injection Gain in Regenerative Operation
0 to 400%
100%
No.
Parameter Name
Setting Range
Default
S3-26
DC Injection Gain in Motoring Operation
0 to 400%
20%
No.
Parameter Name
Setting Range
Default
S3-27
Torque Compensation Value with Load Condition 1
-100.0 to 100.0%
-50.0%
No.
Parameter Name
Setting Range
Default
S3-28
Torque Compensation Value with Load Condition 2
-100.0 to 100.0%
50.0%
No.
Parameter Name
Setting Range
Default
S3-29
Analog Input from Load Sensor with Load Condition 1
-100.0 to 100.0%
0.0%
No.
Parameter Name
Setting Range
Default
S3-30
Analog Input from Load Sensor with Load Condition 2
-100.0 to 100.0%
100.0%